Recalls: Heating and Ventilation and Air Conditioning

December 22, 2021 Royal Sovereign Recalls Portable Air Conditioners Due to Fire and Burn Hazards; One Death Reported

This recall involves the following models of portable air conditioners: Model Numbers PAC-3012 PAC-3012 RB ARP-3012 ARP-3012 KIT ARP-3012S ARP-3014 ARP-3014 SC The model number is printed on the name plate sticker on the back of the portable air conditioners. Read more.


November 18, 2021 Goodman Manufacturing Company Recalls Evaporator Coil Drain Pans Installed with Condensing Gas Furnaces Due to Fire Hazard

This recall involves evaporator coil drain pans paired with residential condensing gas furnaces that are installed in a vertical, or "up-flow," configuration. Furnaces in this configuration that were installed or repaired with a new evaporator coil drain pan between January 2019 and November 2021 are affected by this recall. Only evaporator drain pans with serial numbers with prefixes ranging from 1901 through 2101 are covered by this recall. The evaporator coil, which sits atop the vertically installed furnace, will either be cased or uncased. The evaporator coil's serial number is displayed on a label attached to both cased and uncased models. For cased evaporator coils, the serial number is on the label attached to the coil case. For uncased units, the serial number is on a label attached to the front of the coil. It may be necessary to determine the brand and model number of your existing furnace in order to provide the correct repair kit. In most instances, the furnace brand and model number can be found on your furnace on the "Energy Guide" label. For all other instances, please refer to the instructions on Goodman's model verification tool at: www.recallrtr.com/drainpan The model number of the outdoor condenser your furnace is paired with may also be required. The model number can be found on a label attached to the outdoor condenser. Read more.


November 3, 2021 Usines Giant Factories Recalls Gas Water Heaters with Emerson Control Valves Due to Risk of Carbon Monoxide Poisoning

The recall involves propane and natural gas water heaters in 40, 50, and 75 gallon capacities. The recalled water heaters are white with a red "Giant" logo decal on the front. The water heaters have a nameplate near the Emerson gas control valve with the following model number ranges. UG40-38LFPV2-P1U-US, UG40-40LFPV2-N1U-US, UG50-38LFPV2-P1U-US, UG50-38LFPV2-P2U-US, UG50-38TFPDV1-N2U-US, UG50-40LFPV2-N1U-US, UG50-40LFPV2-N2U-US, UG75-76MEPV1-N2U-US, UG75-76MEPV1-P2U-US. The control valves are black with a white "Emerson" logo on the front. The Emerson control valve model numbers and date code are located on a label on the right-hand side of the bracket holding the Emerson control valve to the gas water heater. The recalled control valve model numbers are 37H73A-301P1 (natural gas) and 37H74A-301P1 (propane) with a date code between 1821 and 1839. Read more.


February 3, 2021 Enerco Group Recalls DeWALT Cordless Kerosene Heaters Due to Fire and Carbon Monoxide Poisoning Hazards

This recall involves DeWALT cordless kerosene forced-air heaters model number DXH90CFAK with serial numbers 340902-20001001 through 340902-20004000 and model number DXH90CFAKM with serial numbers 340901-20001001 through 340901-20001500. The heaters have a black tank/base, a yellow body and a gray combustion barrel. "DeWALT" and "90,000 BTU" are printed in yellow on the combustion barrel. The model number and serial number are located on the side panel opposite the controls. Read more.


October 9, 2020 Westinghouse Lighting Recalls Outdoor Ceiling Fans Due to Impact Injury Hazard (Recall Alert)

This recall involves Westinghouse Lighting's Great Falls 52" outdoor ceiling fans with four dark walnut blades, frosted amber glass and an LED lamp. The fan blades are 22 inches long and have an oil rubbed bronze finish. Model number 72043 and a product order number of 016555, 016761, 016647, 017157, 016648 or 017349 are printed on the top of the fan's motor housing. Read more.


September 16, 2020 MWE Investments Recalls Westinghouse Portable Generators Due to Fire Hazard

This recall involves Westinghouse WGen5300DFv Dual Fuel Portable Generators and Westinghouse iGen4500DF Dual Fuel Inverter Portable Generators with manufacture dates from October 2019 through December 2019. The dual fuel generators can run on gasoline or propane. The WGen5300DFv has a bright blue and black metal exterior and has "Westinghouse" and "WGen5300DFv" printed in white lettering on the control panel on the side of the generator. The generator has a fold down handle and wheels for portability. The generator measures about 23.3 inches long by 20 inches wide inches by 19.29 inches tall without its wheel kit. It weighs about 129 pounds. The iGen4500DF has a bright blue plastic cover and has "Westinghouse iGen4500DF" printed in white lettering on both side panels. The generator measures about 29.7 inches long by 19.7 wide inches by 22 inches tall. It weighs about 105 pounds. Affected units will have one of the following serial numbers, which can be found on the unit's back panel (the "x" fields are specific to individual units): 04511A1019xxxxxxxxx 04511A1219xxxxxxxxx 5311A1219xxxxxxxxx Read more.


July 30, 2020 Miles Industries Recalls Gas Fireplaces Due to Burn and Laceration Hazards (Recall Alert)

This recall involves two models of Valor H5 propane gas fireplaces: Model 1150ILP with serial number ranging from 20001 through 20365 and model 1150JLP with serial number ranging from 20366 through 21502. The recalled fireplaces were sold in seven different trim and front options with a log set and a mesh barrier screen that was installed in front of the glass. The fireplaces are a fully enclosed rectangular sheet metal box with a glass front. The exhaust is vented to the outside through a ventilation duct. The model number and serial number are printed on a rating sheet behind the trim. Read more.


July 28, 2020 Triangle Tube Recalls to Repair Gas Boilers Due to Risk of Carbon Monoxide Hazard; One Death Reported; In-Home Remedy May Be Delayed Due To COVID-19 Restrictions

This recall involves 22 models of the Prestige Solo & Prestige Excellence condensing gas boilers manufactured between November 2011 and October 2019, for residential and light commercial use. These wall-hung condensing gas boilers are housed in a white metal box. The name "Prestige" is printed on the white front panel and on the outside of the cardboard packing box. You can identify whether you have an affected boiler using the firm's "how to" document at www.triangletube.com. The boilers included in this recall have the following serial number ranges: Product Name Models by Prefix Serial Number Range located on Boiler Rating Label Date of Manufacture Prestige Solo -Prefix: PT PT 60, PT110, PT 110LP, PT175, PT250, PT399, PT399HP PT0000110 to PT0053776 or PTA002645 through PTA09800 or AE1100 through AE1239 November 2011 through December 2015 Prestige Solo - Prefix: PA PA80, PA110, PA155, PA175, PA250, PA299, PA399 PA044928 through PA139939 January 2016 through March 2019 Prestige Excellence - Prefix: PTE or PTEA PTE 110 PTE0000568 through PTE 053690 and PTEA002889 through PTEA 003086 November 2011 through December 2015 Prestige Excellence - Prefix: PEA or PEB2 PEA 110 PEB2 110 PEA 078169 through PEA143958 and PEB2157356 through PEB2159813 January 2016 through March 2019 Prestige Solo - Prefix: PB PB80, PB110, PB155, PB175, PB250, PB299, PB399 PB2152110 through PB2163489 April 2019 through October 2019 Read more.


June 18, 2020 Lochinvar Recalls Condensing Residential Boilers Due to Risk of Carbon Monoxide Poisoning

This recall includes residential condensing boilers, combi boilers and packaged systems sold after August 2016. The following model numbers are included in the recall. They were sold under the Lochinvar, A. O. Smith, and State Proline brand names and have serial numbers within the range of 103475818 through 115078306. The model number and serial number can be found on the data plate on the product located on the unit's rating plate, which is located either on the outer jacket of the unit, or on the underside of the removable front jacket plate. The brand name is printed on the front of each unit. Recalled Model Numbers ACB KHB (Cont.) SCB WHL ACB110H-N KHB285L-8647 SCB110H-N WHL156-8647 ACB110H-P KHB285N SCB110H-P WHL200 ACB110S-N KHB285N-001 SCB110S-N WHL286 ACB110S-P KHB285N-002 SCB110S-P WHL286-8647 ACB150H-N KHB285N-8018 SCB150H-N ACB150H-P KHB285N-8647 SCB150H-P WHN ACB150S-N KHB285N-8710 SCB150S-N WHN056 ACB150S-P KHB285N-M7 SCB150S-P WHN056-8647 ACB199H-N SCB199H-N WHN086 ACB199H-P NKB SCB199H-P WHN086-8647 ACB199S-N NKB050L SCB199S-N WHN111 ACB199S-P NKB050L-8647 SCB199S-P WHN111-8647 APN NKB050N WHB WHN156 APN285 NKB050N-8647 WHB055L WHN156-8647 EPB NKB080L WHB055N WHN200 EPB080N NKB080L-8647 WHB055N-8647 WHN200-0119-002 EPB110N NKB080N WHB085L WHN200-8647 EPB110N-CAN NKB080N-8647 WHB085N WHN286 EPB150N NKB110L WHB085N-8647 WHN286-M7 EPB199N NKB110L-8647 WHB110L WHN286-001 EPC NKB110N WHB110N WHN286-8647 EPC110N NKB110N-8647 WHB110N-8647 EPC110N-CAN NKB150L WHB155L EPC150N NKB150L-8647 WHB155N EPC199N NKB150N WHB155N-8018 KHB NKB150N-8647 WHB155N-8647 KHB055L NKB199L WHB199L KHB055N NKB199L-8647 WHB199N KHB055N-8647 NKB199N WHB199N-8018 KHB085L NKB199N-8647 WHB199N-8647 KHB085N WHB285L KHB085N-8647 NKC WHB285L-8647 KHB110L NKC110L WHB285N KHB110N NKC110L-8647 WHB285N-0119-001 KHB110N-8647 NKC110N WHB285N-8647 KHB155L NKC110N-8647 WHB285N-M7 KHB155N NKC150L WHB399L KHB155N-8647 NKC150L-8647 WHB399N KHB199L NKC150N WHB399N-0119-001 KHB199N NKC150N-8647 WHB399N-0119-002 KHB199N-0030-001 NKC199L WHB399N-0119-003 KHB199N-8018 NKC199L-8647 WHB399N/199N-0119-001 KHB199N-8647 NKC199N WHB399N-8647 KHB285L NKC199N-8647 WHB399N-M7 Read more.


March 19, 2020 Plant Therapy Recalls Wintergreen Essential Oils and Essential Oil Blends with Wintergreen Due to Failure to Meet Child Resistant Packaging Requirement; Risk of Poisoning (Recall Alert)

This recall involves 1/3 fl. oz (10 mL), 1 fl. oz (30 mL), and 3.3 fl. oz (100 mL) amber glass bottles with black caps of Plant Therapy Wintergreen (Gaultheria procumbens), Organic Wintergreen (Gaultheria procumbens), Muscle Aid Synergy Blend (undiluted), Tingly Mint Synergy Blend, Vein Aid Synergy Blend (undiluted) sold prior to September 20, 2019. The label on the front of each bottle displays the Plant Therapy logo, product name, and the volume amount of the bottle. The UPC codes are printed on back of the label. Product Name Size UPC Code Plant Therapy Wintergreen 10 mL 610256943879 30 mL 609224262821 100 mL 680912011082 Plant Therapy Organic Wintergreen 10 mL 680912010061 30 mL 680912021562 100 mL 680912000543 Plant Therapy Muscle Aid Synergy Blend (undiluted) 10 mL 610256944296 30 mL 680912022699 100 mL 680912010764 Plant Therapy Tingly Mint Synergy Blend 10 mL 680912022842 30 mL 680912022859 100 mL 609224263347 Plant Therapy Vein Aid Synergy Blend (undiluted) 10 mL 680912022903 30 mL 680912022910 100 mL 680912010795 Read more.